Diesel Generator Set Data
Set Type: XG-400GF
Standby Output: 400KW/500KVA
Prime Output: 364KW/454KVA
Rated Current: 655(A)
Rated Frequency: 50(Hz)
Start-up time: 5~6(s)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230(V)
Standard Features
1. Engine: PERKINS 2506C-E15TAG1
2. Radiator 50℃ max
3. Fans are driven by belt, with safety guard
4. 24V charge alternator
5. Dry type air filter, fuel filter, oil filter
6. Alternator: single bearing alternator
7. IP23, insulation class H/H
8. Main line circuit breaker
9. Standard control panel
10. Absorber
11. Muffler
12. User manual
Diesel Engine Data | ||
Manufacturer: | PERKINS | |
Model: | 2506C-E15TAG1 | |
Standby/Prime Power: | 436KW/396KW | |
Rated Speed: | 1500(r/min) | |
Cycle: | 4 stroke | |
Cylinder Arrangement: | 6 in line | |
Displacement: | 15L | |
Bore and Stroke: | 137*171(mm) | |
Compression Ratio: | 16:1 | |
Governor Type: | Electronic | |
Start battery voltage: | 24V DC | |
Air Intake System | ||
Air Intake System: | Turbo | |
Max Intake Restriction: | ||
Burning Capacity: | 33m³/min | |
Air Flow: | 722 m³/min | |
Exhaust System | ||
Exhaust Gas Flow: | 88m³/min | |
Exhaust Temperature: | 535℃ | |
Max Back Pressure: | 10.2kpa | |
Fuel System | ||
Fuel System: | Direct injection | |
100%( Prime Power) Load: | 216g/kwh | |
50%( Prime Power) Load: | 231g/kwh | |
Oil System | ||
Total Oil Capacity: | 62L | |
Oil Consumption: | ||
Engine Oil Tank Capacity: | ||
Oil Pressure at Rated RPM: | ||
Cooling System | ||
Cooling Way: | Water-cooled | |
Total Coolant Capacity: | 60L | |
Thermostat: | 88-98℃ | |
Max Water Temperature: | 107℃ | |
Alternator Data | ||
Manufacturer: | STARLIGHTSTAMFORD/SIEMENS/MARATHON/ENGGA/KEPU | |
Excitation Mode: | Brushless and self- exciting | |
Number of phase and Access Act: | 3-phase 4-wire | |
Connecting Type: | "Y" type connecting | |
Alternator Capacity: | 500KVA | |
Alternator Efficiencies: | 95% | |
Overload: | (PRP)110% load can run 1h | |
Protection Level: | IP22-IP23 | |
Insulation Class, Temperature Rise: | H/H | |
Telephone Influence Factor (TIF): | <50 | |
THF: | <2% | |
Voltage Regulation, Steady State: | ≤±1% | |
Air Cooling Flow: | 0.216m3/s | |
Altitude: | ≤1000m |